What is the TECO CU-65R?

The CU-65R is a TECO three-pole AC contactor in the 65 A AC-3 class: Ith 100 A, rated to switch 18.5 kW motors at 220/230 V, 30 kW at 380/400 V and 37 kW at 660/690 V, with a 1000 V insulation rating and an E5 coil at 110 V 50/60 Hz. The UL side rates it Size 2 at 600 V AC — 20 to 50 hp by voltage. Three main poles (1/L1-3/L2-5/L3 to 2/T1-4/T2-6/T3), one NO and one NC auxiliary built in, non-reversing, CCC, CE and cULus listed, built by TECO's Taian Science (Wuxi) plant in China. The record covers 5 contactors, new in TECO boxes. All 12 photos and 1 video below show these exact units.

3 min readContent reviewed

Part details

CU-65R, as printed on the faceplate and box
Field Value
Model TECO CU-65R magnetic (AC) contactor, non-reversing
Main poles 3 (1L1/3L2/5L3 to 2T1/4T2/6T3)
Auxiliary 1 NO + 1 NC built in (13-21, 43-31 / 22-14, 32-44); box config 3A2a2b
AC-3 rating Ith 100 A, Ui 1000 V — 18.5 kW @ 220/230 V (65 A), 30 kW @ 380/400 V (64 A), 37 kW @ 660/690 V (45 A)
UL rating Size 2, 3-phase 600 V AC, 100 A — 20/25/50/50 hp at 200/240/480/600 V
Coil Code E5, 110 V, 50/60 Hz
Terminals Main AWG 8-1, 50 lb-in, 75 °C Cu wire only (UL label)
Approvals CCC A000452, CE, cULus US Listed E72215 (268Z IND.CONT.EQ)
Standards GB/T 14048.4, EN/IEC 60947-4-1
Maker TECO — Taian Science & Technology (Wuxi) Co., China
Quantity 5 contactors, new in TECO boxes
Warranty 3 months, as recorded at intake
Shipping weight 1 kg each
Scroll sideways to see the full table.

Every rating is read from the faceplate and the box label in the photo set.

Reading the AC-3 table against the motor

The three-line kW table on the faceplate is the whole sizing exercise for this contactor. AC-3 is the duty of switching a motor already running — the inrush is the contactor's problem for a few cycles, the running current forever — and the table gives the motor power each voltage supports: 30 kW at the 380/400 V European standard, 18.5 kW at 220/230 V, 37 kW at 660/690 V, all inside 45-65 A of actual current. The UL side reads differently because UL Size 2 rates by horsepower: 50 hp at 480 or 600 V — a slightly more generous figure for the same contacts, which is normal between the two systems. The E5 coil at 110 V 50/60 Hz matches the control-transformer voltage common in both Asian and North American panels; other coil codes exist for other control voltages, and matching the coil — not just the contactor — is what a swap requires. The built-in 1 NO + 1 NC auxiliary handles the seal-in contact and the running lamp; the side-mount add-on blocks take it to the 2a2b configuration the box label lists. Five sealed boxes of the same lot make this a matched set for a motor control centre. KOEED stocks the smaller TECO frames too, such as the CU-32R 110 V contactor.

Photos and video

All images below are original KOEED warehouse photos. Click any photo to view it full size.

Five contactors with TECO boxes
The full intake: five CU-65R contactors on foam beside their TECO boxes — main terminals 1L1/3L2/5L3 and 2T1/4T2/6T3, auxiliary legends 13NO 21NC and 43NO 31NC, 22NC 14NO and 32NC 44NO on every face.
Single contactor front
One contactor front-on: TECO CU-65R marking centred, the three-pole main path above and below, auxiliary contact screws at the sides.
Faceplate close-up
The faceplate in full: CU-65R, CCC A000452, GB/T 14048.4 / EN / IEC 60947-4-1, AC-3 table (18.5/30/37 kW by voltage), UL SIZE 2 100 A with the horsepower table, cULus E72215, Aux. Cont. A600 Q300, terminal wire range and the TECO mark.
Box label
The box label: 交流接触器 CU-65R, 3A2a2b, Ui 1000V, 非可逆式 (non-reversing), coil code E5 at 110 V 50/60 Hz, CE and CCC, and the Taian Science (Wuxi) maker line.
Main contacts from top
The main contacts from above: three silver contact sets under their arc chutes, moving arms centred, phase barriers between.
Second faceplate
A second unit's faceplate: identical rating block, crisp print across the UL table.
Contactor bottom
From the bottom: the coil housing, the mounting foot and the orange auxiliary-carrier clip at the base.
Contactor rear in box
The back of a unit still in its box: DIN/screw mount foot and the coil-access panel.
Front face second unit
Second unit front: full terminal legend row visible — 1L1 3L2 5L3 across the top, 2T1 4T2 6T3 along the bottom.
Contact sets close
The contact sets at eye level: silver faces unworn, pressure springs seated.
Third unit terminals
Third unit: the top main terminals with their shrouds and the auxiliary contact block screws.
Boxes stacked
Closing shot: the five TECO boxes stacked, labels uniform across the lot.
Inspection video: the contactors as they were checked at the KOEED warehouse.

Sourcing help

KOEED supplies this product, in active and EOL stock. Send the part number for a quote.

Need a quote for this part?

Send us the part number or article link — we will confirm price, availability and lead time.

WhatsApp us

Related Articles

Torna al blog