LC1K0910B7


Price:
Sale price$50.00 USD

Due to the constant fluctuations in product information, we kindly ask you to contact us before making a purchase to confirm the latest price before placing an order.

  • Business Days Only (Monday through Saturday)
Contact us By email Chat on WhatsApp
safe
Main
range
TeSys
 
product or component type
Contactor
 
product name
TeSys K
 
device short name
LC1K
 
device application
Control
 
contactor application
Motor control
Resistive load
 
Complementary
utilisation category
AC-1
AC-3
AC-4
 
poles description
3P
 
power pole contact composition
3 NO
 
[Ie] rated operational current
9 A at <= 440 V AC AC-3 power circuit
20 A (<= 122 °F (50 °C)) at <= 440 V AC AC-1 power circuit
16 A (<= 158 °F (70 °C)) at 690 V AC AC-1 power circuit
 
control circuit type
AC 50/60 Hz
 
[Uc] control circuit voltage
24 V AC 50/60 Hz
 
motor power kW
2.2 kW at 400 V AC 50/60 Hz AC-4
2.2 kW at 220...230 V AC 50/60 Hz AC-3
4 kW at 380...415 V AC 50/60 Hz AC-3
4 kW at 440 V AC 50/60 Hz AC-3
4 kW at 480 V AC 50/60 Hz AC-3
4 kW at 500...600 V AC 50/60 Hz AC-3
4 kW at 660...690 V AC 50/60 Hz AC-3
 
auxiliary contact composition
1 NO
 
overvoltage category
III
 
[Ith] conventional free air thermal current
20 A at <= 122 °F (50 °C) power circuit
10 A at <= 122 °F (50 °C) signalling circuit
 
Irms rated making capacity
110 A AC power circuit conforming to NF C 63-110
110 A AC power circuit conforming to IEC 60947
110 A AC signalling circuit conforming to IEC 60947
 
rated breaking capacity
110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220...230 V conforming to IEC 60947
110 A at 380...400 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
 
associated fuse rating
25 A gG at <= 440 V power circuit
25 A aM power circuit
10 A gG signalling circuit conforming to IEC 60947
10 A gG signalling circuit conforming to VDE 0660
 
average impedance
3 mOhm at 50 Hz - Ith 20 A power circuit
 
insulation resistance
> 10 MOhm signalling circuit
 
inrush power in VA
30 VA at 68 °F (20 °C)
 
hold-in power consumption in VA
4.5 VA at 68 °F (20 °C)
 
heat dissipation
1.3 W
 
control circuit voltage limits
0.2...0.75 Uc at <= 122 °F (50 °C) drop-out
0.8...1.15 Uc at <= 122 °F (50 °C) operational
 
operating rate
3600 cyc/h
 
auxiliary contacts type
Type instantaneous (1 NO)
 
signalling circuit frequency
<= 400 Hz
 
minimum switching current
5 mA signalling circuit
 
minimum switching voltage
17 V signalling circuit
 
operating time
10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing
 
safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
 
non overlap distance
0.02 in (0.5 mm)
 
mechanical robustness
Shocks contactor closed, on X axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Y axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor closed, on Z axis 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on X axis 6 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Y axis 10 Gn for 11 ms IEC 60068-2-27
Shocks contactor opened, on Z axis 10 Gn for 11 ms IEC 60068-2-27
Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor opened 2 Gn, 5...300 Hz IEC 60068-2-6
 
Environment
product certifications
CSA
UL
 
protective treatment
TC conforming to IEC 60068
TC conforming to DIN 50016
 
operating altitude
6561.68 ft (2000 m) without derating
 
flame retardance
V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102

You may also like